Mail Us at : sales@kitomaindonesia.com | Call Us 021 2851 8059

Inverter Frenic Mega 75kW to 630kW 400V 3-phase

 

 

Kitoma Indonesia - Inverter Fuji Frenic Mega 75kW to 630kW 400V 3-phase

 

Wide Model Variation
 

Basic Type
Suitable for the equipment that uses a peripheral device to suppress noise or harmonics
 

 

EMC filter built-in type
By adopting built-in filter, this type is compliant with European EMC Directives category C3 (2nd Env) 'EN61800-3-2004'.
 

 

Frenic Mega 75kW to 630kW 400V 3-phase

  • FRN75G1E-4A  (75kW 400V 3 phase)
  • FRN90G1E-4A  (90kW 400V 3 phase)
  • FRN110G1E-4A (110kW 400V 3 phase)
  • FRN132G1E-4A (132kW 400V 3 phase)
  • FRN160G1E-4A (160kW 400V 3 phase)
  • FRN200G1E-4A (200kW 400V 3 phase)
  • FRN220G1E-4A (220kW 400V 3 phase)
  • FRN280G1E-4A (280kW 400V 3 phase)
  • FRN315G1E-4A (315kW 400V 3 phase)
  • FRN355G1E-4A (355kW 400V 3 phase)
  • FRN400G1E-4A (400kW 400V 3 phase)
  • FRN500G1E-4A (500kW 400V 3 phase)
  • FRN630G1E-4A (630kW 400V 3 phase)

 

75kW to 630kW High Duty specification for heavy load


Item
Specifications
Type (FRN□□□G1E-4□) 75 90 110 132 160 200 220 280 315 355 400 500 630
Nominal applied motor [kW] (*1) 75 90 110 132 160 200 220 280 315 355 400 500 630
Output ratings Rated capacity [kVA] (*2)
114 134 160 192 231 287 316 396 445 495 563 731 891
Rated voltage [V] (*3)
Three-phase 380 to 480V (with AVR)
Rated Current [A] 150 176 210 253 304 377 415 520 585 650 740 960 1170
Overload capability
150% for 1min, 200% for 3.0s
Rated frequency [Hz]
50, 60Hz
Input ratings Main circuit power
Phases, voltage, frequency
Three-phase 380 to 440V/50Hz
Three-phase 380 to 480V/60Hz
Auxiliary control power input
Phases, voltage, frequency
Single-phase 380 to 480V, 50/60Hz
Auxiliary power input for fan
Phases, voltage, frequency (*5)
Single-phase 380 to 440V/50Hz
Single-phase 380 to 480V/60Hz
Voltage, frequency variations
Voltage:+10 to -15% (Voltage unbalance:2% or less (*6)) Frequency:+5 to -5%
Rated current [A] (*7) with DCR 138 164 201 238 286 357 390 500 559 628 705 881 1115
without DCR
-
-
-
-
-
-
-
-
-
-
-
-
-
Required power supply capacity [kVA] (*8) with DCR 96 114 140 165 199 248 271 347 388 436 489 611 773
Braking Torque [%] (*9)
10 to 15%
Braking transistor
-
Min. ohmic value [Ω]
Torque [%]
-
DC injection braking Starting frequency:0.0 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level:0 to 100%
EMC filter
EMC standard compliance: Category C3 is only emission and 2nd Env. is immunity. (EN61800-3:2004)
DC reactor (DCR) (*10) Standard accessory
Applicable safety standards
UL508C, C22.2No.14 (pending), EN61800-5-1:2003
Enclosure (IEC60529)
IP00 open type, UL open type
Cooling method
Fan cooling
Weight/Mass [kg]
43
                       

 

 

Untuk informasi lebih lanjut silakan hubungi bagian Marketing kami, kami senang untuk membantu :

 

Hubungi : Sales & Marketing
Alamat

: Simprug Plaza

 

  Jl. Simprug Raya Blok B.2 No.5 Cikarang Baru Jababeka II - Bekasi 17530 Jawa Barat - Indonesia

Telepon
: 021 2851 8059
Mobile : 0857 7664 0198 (Sales & Marketing)
Fax : 021 2851 8058
Email sales@kitomaindonesia.com  |  marketing@kitomaindonesia.com  |  scales@kitomaindonesia.com  | kitomascale@gmail.com