3G3RX-V1 3-phase 200VAC Series
Kitoma Indonesia : 3G3RX-V1 3-phase 200VAC Series
High function General purpose Inverters
Enclosure ratings IP20
Versatile for a Wide Range of Applications
- Double rating VT 120%/1 min and CT 150% /1 min
- Drive Programming
- LCD 5 line Digital Operator (optional)
- Fieldbus communications with optional unit EtherCAT, CompoNet and DeviceNet
- Built-in radio noise filter/EMC filter (selectable)
3G3RX-V1 Models
3-phase 200VAC
3G3RX-A2004-V1 : CT = 0.4 kW, VT = 0.75kW
3G3RX-A2007-V1 : CT = 0.75kW, VT = 1.5kW
3G3RX-A2015-V1 : CT = 1.5 kW, VT = 2.2kW
3G3RX-A2022-V1 : CT = 2.2 kW, VT = 3.7kW
3G3RX-A2037-V1 : CT = 3.7 kW, VT = 5.5kW
3G3RX-A2055-V1 : CT = 5.5 kW, VT = 7.5kW
3G3RX-A2075-V1 : CT = 7.5 kW, VT = 11kW
3G3RX-A2110-V1 : CT = 11 kW, VT = 15kW
3G3RX-A2150-V1 : CT = 15 kW, VT = 18.5kW
3G3RX-A2185-V1 : CT = 18.5kW, VT = 22kW
3G3RX-A2220-V1 : CT = 22kW, VT = 30kW
3G3RX-A2300-V1 : CT = 30kW, VT = 37kW
3G3RX-A2370-V1 : CT = 37kW, VT = 45kW
3G3RX-A2450-V1 : CT = 45kW, VT = 55kW
3G3RX-A2550-V1 : CT = 55kW, VT = 75kW
CT = Heavy load
VT = Light load
Features
- RoHS Compliant (standard feature)
- Built-in radio noise filter/EMC filter
- Automatic Energy saving
- Standard feature emergency shutoff fungtion
- Removable control terminal block
- Modbus-RTU
- Vector control with a PG
- 0-Hz domain sensorless vector control
- High starting torque
- PID function
- Double Rating
- Drive Programming
Specifications
3-phase 200-V class | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Model name (3G3RX-) | A2004- V1 | A2007- V1 | A2015- V1 | A2022- V1 | A2037- V1 | A2055- V1 | A2075- V1 | A2110- V1 |
||
Maximum applicable motor capacity (kW) | CT | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | |
VT | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | ||
Rated output capacity (kVA) | 200V | CT | 1.0 | 1.7 | 2.5 | 3.6 | 5.7 | 8.3 | 11.0 | 15.9 |
VT | 1.2 | 2.1 | 3.2 | 4.1 | 6.7 | 10.3 | 15.2 | 20.0 | ||
240V | CT | 1.2 | 2.0 | 3.1 | 4.3 | 6.8 | 9.9 | 13.3 | 19.1 | |
VT | 1.5 | 2.6 | 3.9 | 4.9 | 8.1 | 12.4 | 18.2 | 24.1 | ||
Rated input voltage | 3-phase 200 V -15% to 240 V +10%, 50/60 Hz ± 5% | |||||||||
Rated input current (A) | CT | 3.3 | 5.5 | 8.3 | 12 | 18 | 26 | 35 | 51 | |
VT | 3.9 | 7.2 | 10.8 | 13.9 | 23 | 37 | 48 | 64 | ||
Rated output voltage | 3-phase 200 to 240 V (Cannot exceed that of incoming voltage) | |||||||||
Rated output current (A) | CT | 3.0 | 5.0 | 7.5 | 10.5 | 16.5 | 24 | 32 | 46 | |
VT | 3.7 | 6.3 | 9.4 | 12 | 19.6 | 30 | 44 | 58 | ||
EMC Noise Filter | Built-in (EMC Directive EN61800-3 Category C3) | |||||||||
Weight (kg) | 3.5 | 3.5 | 3.5 | 3.5 | 3.5 | 6 | 6 | 6 | ||
Braking Resistor circuit | Regenerative braking |
Built-in Braking Resistor circuit (separate Discharge Resistor) | ||||||||
Min. connectable resistance (Ω) |
50 | 50 | 35 | 35 | 35 | 16 | 10 | 10 | ||
Maximum leakage current (mA) | EMC filter enabled |
2.5 | 48 | |||||||
EMC filter disabled |
0.1 |
3-phase 200-V class | |||||||||
---|---|---|---|---|---|---|---|---|---|
Model name (3G3RX-) | A2150-V1 | A2185-V1 | A2220-V1 | A2300-V1 | A2370-V1 | A2450-V1 | A2550-V1 | ||
Maximum applicable motor capacity (kW) | CT | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 | |
VT | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 | ||
Rated output capacity (kVA) | 200V | CT | 22.1 | 26.3 | 32.9 | 41.9 | 50.2 | 63.0 | 76.2 |
VT | 25.2 | 29.4 | 39.1 | 48.4 | 58.5 | 72.7 | 93.5 | ||
240V | CT | 26.6 | 31.5 | 39.4 | 50.2 | 60.2 | 75.6 | 91.4 | |
VT | 30.3 | 35.5 | 46.9 | 58.1 | 70.2 | 87.2 | 112.2 | ||
Rated input voltage | 3-phase 200 V -15% to 240 V +10%, 50/60 Hz ± 5% | ||||||||
Rated input current (A) | CT | 70 | 84 | 105 | 133 | 160 | 200 | 242 | |
VT | 80 | 94 | 120 | 150 | 186 | 240 | 280 | ||
Rated output voltage | 3-phase 200 to 240 V (Cannot exceed that of incoming voltage) | ||||||||
Rated output current (A) | CT | 64 | 76 | 95 | 121 | 145 | 182 | 220 | |
VT | 73 | 85 | 113 | 140 | 169 | 210 | 270 | ||
EMC Noise Filter | Built-in (EMC Directive EN61800-3 Category C3) | ||||||||
Weight (kg) | 14 | 14 | 14 | 22 | 30 | 30 | 43 | ||
Braking Resistor circuit | Regenerative braking |
Built-in Braking Resistor circuit (separate Discharge Resistor) |
Separate Regenerative Braking Unit | ||||||
Min. connectable resistance (Ω) |
7.5 | 7.5 | 5 | --- | |||||
Maximum leakage current (mA) | EMC filter enabled |
23 | |||||||
EMC filter disabled |
0.1 |
Regenerative Braking Units
3G3AX-RBU21 : General purpose with Braking resistor
3G3AX-RBU22 : High Regenerations purpose with Braking resistor
3G3AX-RBU23 : General purpose for 30kW
3G3AX-RBU24 : General purpose for 55kW
Braking Resistor
Compact type
3G3AX-RBA1201 : Resistor 120W, 180W
3G3AX-RBA1202 : Resistor 120W, 100W
3G3AX-RBA1203 : Resistor 120W, 50W
3G3AX-RBA1204 : Resistor 120W, 35W
Standard type
3G3AX-RBB2001 : Resistor 200W, 180W
3G3AX-RBB2002 : Resistor 200W, 100W
3G3AX-RBB3001 : Resistor 300W, 50W
3G3AX-RBB4001 : Resistor 400W, 35W
Medium capacity type
3G3AX-RBC4001 : Resistor 400W, 50W
3G3AX-RBC6001 : Resistor 600W, 35W
3G3AX-RBC12001 : Resistor 1200W, 17W
Input Noise Filter
3G3AX-NFI21 : 0.4kW - 0.75kW
3G3AX-NFI22 : 1.5kW
3G3AX-NFI23 : 2.2kW - 3.7kW
3G3AX-NFI24 : 5.5kW
3G3AX-NFI25 : 7.5kW
3G3AX-NFI26 : 11kW
3G3AX-NFI27 : 15kW
3G3AX-NFI28 : 18.5kW
3G3AX-NFI29 : 22kW - 30kW
3G3AX-NFI2A : 37kW
3G3AX-NFI2B : 45kW
3G3AX-NFI2C : 55kW
Untuk informasi lebih lanjut silakan hubungi bagian Marketing kami, kami senang untuk membantu :
Hubungi | : Sales & Marketing |
Alamat |
: Simprug Plaza |
Jl. Simprug Raya Blok B.2 No.5 Cikarang Baru Jababeka II - Bekasi 17530 Jawa Barat - Indonesia |
|
Telepon |
: 021 2851 8059 |
Mobile | : 0857 7664 0198 (Sales & Marketing) | 0812 1165 3673 |
Fax | : 021 2851 8058 |
: sales@kitomaindonesia.com | marketing@kitomaindonesia.com | scales@kitomaindonesia.com | kitomascale@gmail.com |